Description
Brief introduction:
ADAM-6217 is an 8-channel analog input module, integrated with 2 more Ethernet ports.
The ADAM-6217 module is powered by Peer-to-Peer (P2P) networking and Graphic Condition Logic that acts as a standalone device for measurement, control and automation.
With industry standard design, support for Modbus TCP, TCP/IP, UDP, HTTP, DHCP and web languages XML, HTML 5, Javascript, ADAM-6217 can be a good integrated I/O solution in the Ethernet control system.
Specifications:
Analog Input | |
Channels | 8 (differential) |
Input Impedance | > 10 MW (voltage) 120 W (current) |
Input Type | mV, V, mA |
lnput Range | ±150 mV, ±500 mV, ±1 V, ±5 V, ±10 V, 0 ~ 20 mA, 4 ~ 20 mA, ±20 mA |
Span Drift | ± 30 ppm/°C |
Zero Drift | ± 6 μV/°C |
Resolution | 16-bit |
Accuracy | ± 0.1% of FSR (Voltage) at 25°C ± 0.2% of FSR (Current) at 25°C |
Sampling Rate | 10 sample/ second (total) |
CMR @ 50/60 Hz | 92 dB |
NMR @ 50/60 Hz | 67 dB |
Common Mode | 200 VDC |
Ordering Information | |
ADAM-6217 | 8-ch Isolated Analog Input Modbus TCP Module |
General | |
Ethernet | 2-port 10/100 Base-TX (for Daisy Chain) |
Protocol | Modbus TCP, TCP/IP, UDP, HTTP, DHCP,RESTful, SNMP (B version), MQTT (B version) |
Connector | Plug-in 5P/15P screw terminal blocks |
Power Input | 10 – 30 VDC (24 VDC standard) |
Watchdog Timer | System (1.6 seconds) Communication (Programmable) |
Power Input | 10 ~ 30 VDC |
Dimensions | 70 x 122 x 27 mm |
Protection | Built-in TVS/ESD protection Power Reversal protection Isolation protection: 2500 VDC |
Power Consumption | 3.5W @ 24 VDC |
Features | |
Daisy chain connection with auto-bypass protection | |
Remote monitoring and control with smart phone/pad | |
Group configuration capability for multiple module setup | |
Flexible user-defined Modbus address | |
Intelligent control ability by Peer-to-Peer and GCL function | |
Multiple protocol support: Modbus TCP, TCP/IP, UDP, HTTP, DHCP, RESTful SNMP (B version), MQTT (B version) | |
Web language support: XML, HTML 5, Java Script | |
System configuration backup | |
User Access Control | |
Environment | |
Operating Temperature | -10 ~ 70°C (14 ~ 158°F) -40 ~ 70°C (-40~158°F) (B version) |
Storage Temperature | -20 ~ 80°C (-4 ~ 176°F) -40 ~ 85°C ( -40~185°F) (B version) |
Operating Humidity | 20 ~ 95% RH (non-condensing) |
Storage Humidity | 0 ~ 95% RH (non-condensing) |
Reviews